Temperature mapping is a study that measures temperature at many points in a space over a set period, to check that the whole space stays within the required range and to find its coldest and warmest spots. It applies to cold rooms, warehouses, refrigerators and transport vehicles.
Good Distribution Practice for medicines requires an initial mapping of the storage area before use, under representative conditions. Monitoring probes are then placed where the mapping recorded the largest fluctuations. For example, the mapping of cold room CF-07 shows that the area near the door exceeds 8 °C during loading hours, so a fixed probe is installed there.
Mapping is repeated according to a risk assessment or whenever a significant change is made to the facility or the cooling equipment. Its reports, together with the certificates of the probes used, are part of the documentation reviewed in an inspection.